SCHEDULED OUTAGED PRIVILEGIATA
SCHEDULED OUTAGED PRIVILEGED POWER ----> NORMAL POWER SUPPLYCHECK LIST
o All PCs OFF
o ION GAUGES OFF, COMIX GAUGE OFF. CONTROLLER ION GAUGES TO NORMAL
o TURBO LOAD LOCK OFF
o VALVE SCROLL MAIN CLOSED
o SCROLL MAIN OFF CONTROLLER PRIV to NORM. SCROLL MAIN ON
o VALVE SCROLL MAIN OPEN
o VALVE SCROLL PREP CLOSED
o SCROLL PREP OFF, CONTROLLER PRIV to NORM. SCROLL PREP ON
o VALVE SCROLL PREP OPEN
o CLOSE VALVES PREP AND MAIN. CONTROLLER VALVES PRIV to NORM
o TURBO MAIN OFF
o CONTROLLER MAIN PRIV to NORM
o TURBO MAIN ON
o TURBO PREP OFF
o CONTROLLER PREP PRIV to NORM
o TURBO PREP ON
o VALVE SCROLL MANIP AND COMIX CLOSED
o SCROLL COMIX OFF, CONTROLLER PRIV to NORM. SCROLL COMIX ON
o VALVE SCROLL MAINP AND COMIX OPEN
o TURBO COMIX OFF
o CONTROLLER COMIX PRIV to NORM
o TURBO COMIX ON
o TURBO MANIP OFF (menu, select ¿PUMP STATUS, menu, PUMP STATUS ¿, SYSTEM ON—press symbol Öto get SYSTEM OFF.
o CONTROLLER MANIP PRIV to NORM
o TURBO MANIP ON (then back to the main menu to check the status)
o
o TURBO CART OFF
o CONTROLLER TURBO CART PRIV to NORM
o TURBO CART ON
o CONNECT POWER CABLE TO NORMAL AND DISCONNECT POWER CABLE EATON FROM PRIV
SCHEDULED SWITCH NORMAL POWER ----> PRIVILEGED POWER SUPPLY
CHECK LIST
o All PCs OFF
o ION GAUGES OFF, COMIX GAUGE OFF. CONTROLLER ION GAUGES TO NORMAL
o TURBO LOAD LOCK OFF
o VALVE SCROLL MAIN CLOSED
o SCROLL MAIN OFF CONTROLLER NORM TO PRIV. SCROLL MAIN ON
o VALVE SCROLL MAIN OPEN
o VALVE SCROLL PREP CLOSED
o SCROLL PREP OFF, CONTROLLER NORM TO PRIV. SCROLL PREP ON
o VALVE SCROLL PREP OPEN
o CLOSE VALVES PREP AND MAIN. CONTROLLER VALVES NORM TO PRIV. TURBO MAIN OFF
o CONTROLLER MAIN NORM TO PRIV.
o TURBO MAIN ON
o
o TURBO PREP OFF
o CONTROLLER PREP NORM TO PRIV.
o TURBO PREP ON
o VALVE SCROLL MANIP AND COMIX CLOSED
o SCROLL COMIX OFF, CONTROLLER NORM TO PRIV.. SCROLL COMIX ON
o VALVE SCROLL MAINP AND COMIX OPEN
o TURBO COMIX OFF
o CONTROLLER COMIX NORM TO PRIV.
o TURBO COMIX ON
o TURBO MANIP OFF (menu, select PUMP STATUS, menu, PUMP STATUS, SYSTEM ON—press symbol Öto get SYSTEM OFF.
o CONTROLLER MANIP PRIV to NORM
o TURBO MANIP ON (then back to the main menu to check the status)
o
o TURBO CART OFF
o CONTROLLER TURBO CART NORM TO PRIV. TURBO CART ON
o CONNECT POWER CABLE TO PRIVILEG AND DISCONNECT POWER CABLE EATON FROM NORMAL